Integrations
Allen-Bradley (EtherNet/IP) to MQTT, without a script.
Read ControlLogix, CompactLogix or Micro800 tags by name with MaestroHub's EtherNet/IP connector, including whole UDTs, and publish them to your MQTT broker on topics from the plant model with unit and quality.
The flow
One value, from the machine to MQTT. Illustrative.
Allen-Bradley (EtherNet/IP)PLC protocolProgram:Line2.Filler.Speed
MaestroHubFiller 2 speed · 412 bpm · Good
- named, unit, quality
- origin stamped
- buffered on disk
MQTTmessage brokerplant/line2/filler2/speedWhy do it with MaestroHub
More than a pipe from Allen-Bradley (EtherNet/IP) to MQTT.
Tags by name, UDTs whole
Read structures as they are in the controller, without unpacking them by hand.
Batch reads that stay honest
Many tags in one call, each with its own result, so one bad tag never hides the others.
Mixed plants, one broker
Allen-Bradley lines publish next to Siemens and Modbus equipment in the same structure.
What lands in MQTT
An example. You choose the fields in the pipeline.
| topic | value | unit | quality | ts |
|---|---|---|---|---|
| plant/line2/filler2/speed | 412 | bpm | good | 2026-10-03T06:00:01Z |
Set it up in three steps
- 1
Connect Allen-Bradley (EtherNet/IP)
Add the controller, list its tags with their types and pick the ones you need; a batch read fetches many in one call.
- 2
Give the values meaning
Map each value to a topic in the namespace with its name, unit and schema. Quality and origin are stamped on every value.
- 3
Deliver to MQTT
Add an MQTT publish output with a topic template, so every value lands on a clean, predictable topic.
Before you start
What each side needs, from the connector documentation.
Allen-Bradley (EtherNet/IP)
- MaestroHub must reach the controller on TCP port 44818. For a ControlLogix, use the Ethernet module's address, for example a 1756-EN2T.
- The controller family (Logix or Micro800) and, for Logix, the CPU slot: 0 for a CompactLogix, the physical slot for a ControlLogix.
- Tags whose External Access in Studio 5000 is not None. Read Only tags and constants refuse writes.
- The tag names from the controller program, found with Browse Tags or a Studio 5000 .L5X export.
Example settings
- PLC Host
- 192.168.1.10
- Port
- 44818
- Controller Family
- Logix
- PLC Slot
- 0
- Timeout (ms)
- 5000
- Keep-Alive Interval (ms)
- 10000
MQTT
- A reachable MQTT broker: hostname, port (typically 1883 plain, 8883 for TLS) and protocol tcp, ssl, ws or wss.
- Broker credentials if the broker requires them. A password needs a username.
- For verified TLS or mutual TLS: the CA certificate, client certificate and private key in PEM format.
Example settings
- Protocol
- ssl
- Broker Hostname
- broker.example.com
- Port
- 8883
- MQTT Version
- 3.1.1
- Client ID
- <your-client-id>
- Keep Alive (sec)
- 60
Things to know
Pitfalls and limits the documentation calls out, so they don't surprise you on site.
Allen-Bradley (EtherNet/IP)
- The data type must match the tag, or the read is refused with the tag's real type. Use auto when you do not know the type.
- Program-scoped tags need the Program:<Program>.<Tag> prefix. Without it the controller answers CIP status 0x04, not found.
- A Micro800 accepts up to 16 connections at a time and exposes only global variables. Keep the number of MaestroHub connections and other clients to one controller small.
Limits
- SLC 500, MicroLogix and PLC-5 (PCCC controllers) are not supported. Cyclic class 1 I/O connections are not used.
- Writing a single bit of an integer or a whole structure (UDT) is not supported: write the integer or the members. A STRING write stores up to 82 characters.
MQTT
- Plain ws cannot use TLS. Use wss for TLS over WebSocket.
- The certificate fields appear only when TLS is on and certificate verification is not skipped.
- On MQTT 5.0, write a shared subscription in the topic filter to load-balance across clients: $share/<group>/<topic>.
Limits
- Reconnection, subscription recovery and message acknowledgement are handled by the platform and cannot be configured on the connection.
What teams use it for
Unified namespace on Rockwell lines
Logix controllers feeding the broker the whole plant uses.
OEE from PLC states
Run, idle and fault states per machine.
Pick tags offline
Load a Studio 5000 export to choose tags before you are on site.
Ways to connect Allen-Bradley (EtherNet/IP) to MQTT
In general terms. Check any specific product for its own details.
Compare a custom script, a flow tool, a cloud vendor's edge service and MaestroHub
Swipe sideways to see every column
| A custom script | A flow tool | A cloud vendor's edge service | MaestroHub | |
|---|---|---|---|---|
| Talks Allen-Bradley (EtherNet/IP) | A library you choose | Community plug-ins | Depends on the vendor | Built in, one of 90+ connectors |
| Names, units and schema | You write it | You build it | Partly, in the vendor's model | One governed namespace |
| Quality on every value | You write it | You build it | Depends on the vendor | Built in, carried through calculations |
| Where each value came from | You write it | You build it | Depends on the vendor | Stamped on every value |
| Survives a network outage | You build it | You build it | Usually, to that vendor's cloud | On disk, per destination, in order |
| Several destinations at once | One script each | Yes, flow by flow | Mostly that vendor's cloud | Any mix, each with its own buffer |
| Permissions and audit | You build it | You build it | Cloud account permissions | Roles, single sign-on, audit trail |
| AI agents can use the data | You build it | You build it | Depends on the vendor | Through the MCP server |
Questions
How do I publish Allen-Bradley ControlLogix tags to MQTT?
Read ControlLogix, CompactLogix or Micro800 tags by name with MaestroHub's EtherNet/IP connector, including whole UDTs, and publish them to your MQTT broker on topics from the plant model with unit and quality.
Do I need to write code to connect Allen-Bradley (EtherNet/IP) to MQTT?
No. You configure the Allen-Bradley (EtherNet/IP) connection and the MQTT output in MaestroHub and join them with a pipeline. Transformations can be added where you need them.
Where does MaestroHub run for this?
On your own infrastructure next to the machines: an edge box, a virtual machine or Kubernetes. Nothing has to leave your network.
Why not just write a script for Allen-Bradley (EtherNet/IP) to MQTT?
A script works on day one. The cost comes later: decoding and naming values, handling bad quality, buffering through outages, keeping credentials safe, and doing it again for the next machine and the next destination. MaestroHub does those once, for every connector.
What else can Allen-Bradley (EtherNet/IP) data go to?
More than 90 connectors are included in every edition, among them historians, databases, cloud warehouses, message brokers and business systems, so the same values can feed several destinations at once.
Try Allen-Bradley (EtherNet/IP) to MQTT yourself.
The free trial includes every connector. No factory to hand? The Digital Factory Simulator serves OPC UA, Modbus, MQTT and more on your laptop.